Safety & Lifesaving

Foam and CO2 Systems

Foam and CO2 Systems covers high-pressure CO2 total flooding systems for machinery spaces and pump rooms, low-pressure CO2 tanks, helideck foam systems, and foam proportioners, monitors, generators, tanks and concentrate. CO2 banks are long-lived pressure equipment with strict test dates. Foam concentrate ages, and older fluorinated foams now face outright bans. Check both before you treat used stock as an asset.

How CO2 and foam put out fires

A CO2 total flooding system fills a closed space with carbon dioxide until the oxygen level is too low for combustion. The concentration that does this is lethal to people. The space must be evacuated before release, so the system has two separate release controls, a time delay and a pre-discharge alarm. Under the FSS Code the alarm sounds for at least 20 seconds before the gas is released.

A foam system mixes concentrate with firewater through a proportioner and expands it with air. The foam blankets a burning liquid, cuts off oxygen and stops vapour release. Low-expansion foam suits helidecks and fuel areas. High-expansion foam fills an enclosed machinery space.

Configurations

TypeHow it worksWhere it fits
High-pressure CO2 bankCylinders at ambient temperature, manifold, pilot releaseMachinery spaces, pump rooms, paint stores
Low-pressure CO2Refrigerated bulk tankLarge protected volumes
Helideck foam, fixed monitorsLow-expansion foam from deck-edge monitorsHelidecks
Deck-integrated helideck foamPop-up nozzles in the deckHelidecks, often unattended
High-expansion foamGenerators flood the spaceMachinery spaces

Key specifications

ParameterWhy it mattersTypical units
CO2 quantitySized on the gross volume of the largest protected spacekg or lb
Cylinder size and fillBank layout and handlingLitres, kg
Foam type and induction rateConcentrate must match the proportioner setting1, 3 or 6 percent
Application rateHelideck and fuel area designL/min/m2
Foam approvalFresh and seawater performanceFSS Code chapter, listing

Standards and service intervals

Chapter 5 of the FSS Code covers CO2. For machinery spaces, 85 percent of the gas must discharge within 2 minutes. IMO MSC.1/Circ.1318/Rev.1 sets CO2 maintenance:

Foam systems fall under FSS Code chapter 6 for machinery spaces, chapter 14 for deck foam and chapter 17 for helicopter facilities. MSC.1/Circ.1312 requires the first lab test of concentrate no more than three years after supply, then every year. On UK helidecks, CAP 437 applies and the 2009 MODU Code has its own helicopter facilities chapter.

PFOS and PFAS rules for foam

From 1 January 2026, SOLAS chapter II-2 as amended by MSC.532(107) bans using or storing extinguishing media containing PFOS above 10 mg/kg. Removed media goes to a shore reception facility. The EU Regulation (EU) 2025/1988 restricts all PFAS in firefighting foams, with transition periods by use. Older AFFF and film-forming fluoroprotein concentrates are now a disposal liability. A fluorine-free replacement may need a different induction rate, nozzles or approval, so confirm the system is approved with it.

Failure modes and inspection

Documentation

Integration and compatibility

A replacement cylinder must match the valve type, pilot actuation and manifold of the installed bank. Check CO2 room space, ventilation and floor loading. Foam skids need a firewater supply that covers the foam demand plus other systems running at the same time. Monitors and nozzles must match the helideck size and the concentrate approval.

Recertification and buying used

Used CO2 cylinders with recent test stamps are worth buying as like-for-like replacements. Older banks will need hydrostatic testing soon after purchase. Unused surplus foam skids and monitors from cancelled projects are good buys if they suit a fluorine-free concentrate. Old fluorinated concentrate is worth less than its disposal cost. Naventr can arrange an inspection of a cylinder bank or foam skid on request. Kidde and Minimax supply CO2 and foam systems. For gas and mist alternatives, see fixed fire suppression.

FAQ

Frequently asked questions

How often do CO2 fire system cylinders need a hydrostatic test?

Under MSC.1/Circ.1318/Rev.1, every cylinder is tested before its 20th anniversary and every ten years after. At the ten-year inspection at least 10 percent are tested, rising if any fail. Contents are checked every two years.

Can used CO2 cylinders be reused in a marine fire system?

Yes, if they match the approved system's valve and actuation and pass a hydrostatic test where one is due. Check the stamped test date on each cylinder, since a bank close to its 20th anniversary needs testing soon.

How often does foam concentrate need testing?

Under MSC.1/Circ.1312, the first lab test is due no more than three years after the concentrate is supplied, then every year. Ask for the last report and a PFOS-free certificate before buying used concentrate or a filled tank.

Can I still use AFFF on an offshore helideck?

Not if it contains PFOS, which SOLAS bans from 1 January 2026. Other fluorinated foams face EU PFAS restrictions with transition periods. Check your flag and the foam's approval before reusing stock, and plan for fluorine-free replacement.