Safety & Lifesaving
Foam and CO2 Systems
Foam and CO2 Systems covers high-pressure CO2 total flooding systems for machinery spaces and pump rooms, low-pressure CO2 tanks, helideck foam systems, and foam proportioners, monitors, generators, tanks and concentrate. CO2 banks are long-lived pressure equipment with strict test dates. Foam concentrate ages, and older fluorinated foams now face outright bans. Check both before you treat used stock as an asset.
How CO2 and foam put out fires
A CO2 total flooding system fills a closed space with carbon dioxide until the oxygen level is too low for combustion. The concentration that does this is lethal to people. The space must be evacuated before release, so the system has two separate release controls, a time delay and a pre-discharge alarm. Under the FSS Code the alarm sounds for at least 20 seconds before the gas is released.
A foam system mixes concentrate with firewater through a proportioner and expands it with air. The foam blankets a burning liquid, cuts off oxygen and stops vapour release. Low-expansion foam suits helidecks and fuel areas. High-expansion foam fills an enclosed machinery space.
Configurations
| Type | How it works | Where it fits |
|---|---|---|
| High-pressure CO2 bank | Cylinders at ambient temperature, manifold, pilot release | Machinery spaces, pump rooms, paint stores |
| Low-pressure CO2 | Refrigerated bulk tank | Large protected volumes |
| Helideck foam, fixed monitors | Low-expansion foam from deck-edge monitors | Helidecks |
| Deck-integrated helideck foam | Pop-up nozzles in the deck | Helidecks, often unattended |
| High-expansion foam | Generators flood the space | Machinery spaces |
Key specifications
| Parameter | Why it matters | Typical units |
|---|---|---|
| CO2 quantity | Sized on the gross volume of the largest protected space | kg or lb |
| Cylinder size and fill | Bank layout and handling | Litres, kg |
| Foam type and induction rate | Concentrate must match the proportioner setting | 1, 3 or 6 percent |
| Application rate | Helideck and fuel area design | L/min/m2 |
| Foam approval | Fresh and seawater performance | FSS Code chapter, listing |
Standards and service intervals
Chapter 5 of the FSS Code covers CO2. For machinery spaces, 85 percent of the gas must discharge within 2 minutes. IMO MSC.1/Circ.1318/Rev.1 sets CO2 maintenance:
- Contents of each cylinder checked every two years by weight or level gauge
- At ten years, at least 10 percent of cylinders internally inspected and hydrostatically tested, rising to 50 percent and then all if any fail
- Every cylinder hydrostatically tested before its 20th anniversary and every ten years after
- Flexible hoses replaced at the maker's interval and at least every ten years
Foam systems fall under FSS Code chapter 6 for machinery spaces, chapter 14 for deck foam and chapter 17 for helicopter facilities. MSC.1/Circ.1312 requires the first lab test of concentrate no more than three years after supply, then every year. On UK helidecks, CAP 437 applies and the 2009 MODU Code has its own helicopter facilities chapter.
PFOS and PFAS rules for foam
From 1 January 2026, SOLAS chapter II-2 as amended by MSC.532(107) bans using or storing extinguishing media containing PFOS above 10 mg/kg. Removed media goes to a shore reception facility. The EU Regulation (EU) 2025/1988 restricts all PFAS in firefighting foams, with transition periods by use. Older AFFF and film-forming fluoroprotein concentrates are now a disposal liability. A fluorine-free replacement may need a different induction rate, nozzles or approval, so confirm the system is approved with it.
Failure modes and inspection
- Cylinder corrosion at the base and under the brackets
- Leaking cylinder valves, found by weight loss
- Release cabinet switches, pull cables, pilot cylinders and time delay
- Manifold check valves and directional valves
- Foam concentrate out of specification on lab test
- Proportioners and monitors seized from seawater and salt
- Foam tank internal coating and bladder condition
Documentation
- Cylinder test certificates with serial numbers and stamped dates
- Last contents check and service report
- System approval, calculation and drawings
- Foam concentrate type, batch, supply date and last lab report
- PFOS-free certificate for any foam concentrate
Integration and compatibility
A replacement cylinder must match the valve type, pilot actuation and manifold of the installed bank. Check CO2 room space, ventilation and floor loading. Foam skids need a firewater supply that covers the foam demand plus other systems running at the same time. Monitors and nozzles must match the helideck size and the concentrate approval.
Recertification and buying used
Used CO2 cylinders with recent test stamps are worth buying as like-for-like replacements. Older banks will need hydrostatic testing soon after purchase. Unused surplus foam skids and monitors from cancelled projects are good buys if they suit a fluorine-free concentrate. Old fluorinated concentrate is worth less than its disposal cost. Naventr can arrange an inspection of a cylinder bank or foam skid on request. Kidde and Minimax supply CO2 and foam systems. For gas and mist alternatives, see fixed fire suppression.
FAQ
Frequently asked questions
How often do CO2 fire system cylinders need a hydrostatic test?
Under MSC.1/Circ.1318/Rev.1, every cylinder is tested before its 20th anniversary and every ten years after. At the ten-year inspection at least 10 percent are tested, rising if any fail. Contents are checked every two years.
Can used CO2 cylinders be reused in a marine fire system?
Yes, if they match the approved system's valve and actuation and pass a hydrostatic test where one is due. Check the stamped test date on each cylinder, since a bank close to its 20th anniversary needs testing soon.
How often does foam concentrate need testing?
Under MSC.1/Circ.1312, the first lab test is due no more than three years after the concentrate is supplied, then every year. Ask for the last report and a PFOS-free certificate before buying used concentrate or a filled tank.
Can I still use AFFF on an offshore helideck?
Not if it contains PFOS, which SOLAS bans from 1 January 2026. Other fluorinated foams face EU PFAS restrictions with transition periods. Check your flag and the foam's approval before reusing stock, and plan for fluorine-free replacement.