Fixed Fire Suppression covers clean agent and inert gas total flooding systems, high and low-pressure water mist, local application systems and galley fryer systems for enclosed spaces on rigs and vessels. Each is approved as a complete design with its own nozzles, valves and design manual. A used system keeps its value only if it is complete or matches an installed system part for part. CO2 has its own sub-Category.

How the system types put out a fire

Clean agent systems discharge a halocarbon such as HFC-227ea or FK-5-1-12 into a closed space. The agent removes heat and interrupts the combustion chemistry, and leaves no residue on electronics. Inert gas systems such as IG-541 and IG-55 dilute the oxygen in the room to a level that will not support flame. Water mist systems spray very fine droplets that cool the fire and displace oxygen locally with steam, using far less water than sprinklers. Local application systems are water-based systems aimed at high-risk spots inside a large machinery space, and you can release them without evacuating the space.

Configurations

TypeTypical storageWhere it fits
Halocarbon clean agentLiquid in containers superpressurised with nitrogen, commonly 25 or 42 barSwitchboard, control and electronics rooms
Inert gasGas in cylinders at 200 or 300 barElectrical rooms, larger enclosed spaces
High-pressure water mistPump skid or cylinders, high-pressure stainless pipeMachinery spaces, generator enclosures
Low-pressure water mistPump skid, larger pipeMachinery and accommodation spaces
Local applicationWater mist or spray on the fire main or own skidEngine tops, purifiers, boiler fronts
Galley fryer systemWet chemical cylinderDeep-fat fryers and hood ducts

Key specifications

ParameterWhy it mattersTypical units
Protected volume and design concentrationSets agent quantity and cylinder countm3 or ft3, percent by volume
Discharge timeApproval criteria for each agent typeSeconds
Storage pressureCylinder and valve classbar or psi
Nozzle type and countFixed by the approved design manualModel, quantity
Pump flow and pressure, for mistCovers the largest sectionL/min, bar

Standards and approvals

The type approval certificate names the maker's design manual and its limits. Check that it is current and that the system was built inside them.

Agent supply and environmental rules

3M has stopped making Novec 1230. FK-5-1-12 is still sold by other producers, but the system approval must cover the agent you refill with. HFC-227ea falls under HFC phase-down in the EU and under the Kigali Amendment. Inert gas and water mist carry no such supply risk. Halon has been banned from new installations under SOLAS for decades.

Failure modes and inspection

Documentation

Integration and compatibility

A gas system needs a room that holds its concentration, ventilation shutdown on release and safe access for the people who must leave first. The release panel must take signals from your fire detection and talk to your fire and gas logic. Mist systems need fresh water and a power supply rated for the pump. Pipe runs must stay within the design manual's limits on length, height and fittings.

Refurbishment and buying used

A complete unused package from a cancelled project, with its calculations, is the best surplus buy. Used systems make most sense as spares for an identical installation. Recertification means retesting cylinders that are due, refilling with an approved agent, new seals and hoses, and a full function test. Naventr can arrange an inspection of a system on request. Marioff and Danfoss Fire Safety are known for marine water mist, and Kidde and Minimax supply gas systems. For machinery spaces where CO2 is still the norm, see foam and CO2 systems.

FAQ

Frequently asked questions

Can I buy a used FM-200 or Novec 1230 system for a rig?

Yes, if the system is complete and its marine type approval is still valid. The approval covers the whole design, so mismatched nozzles or valves can void it. 3M has stopped making Novec 1230, so confirm that the approval covers an FK-5-1-12 agent you can buy.

Which IMO rules apply to water mist systems in machinery spaces?

IMO MSC/Circ.1165, as amended by later circulars, sets approval of water mist systems that replace gas in machinery spaces. Chapter 7 of the FSS Code applies. Local application systems are approved under MSC/Circ.913.

When is a local application fire system required?

SOLAS chapter II-2 regulation 10.5.6 requires one in category A machinery spaces above 500 m3 on cargo ships of 2,000 gross tonnage and above. It protects engine tops, purifiers and boiler fronts and can be released without evacuating the space.

How fast must a clean agent system discharge?

Under MSC/Circ.848 as amended, a halocarbon system must reach 95 percent of its design concentration within 10 seconds. An inert gas system must reach 85 percent within 2 minutes. A used system must still meet these with your pipework.