Fire Pumps and Hydrants
Fire Pumps and Hydrants covers main and emergency firewater pumps with their diesel, electric or hydraulic drivers, jockey pumps, controllers, and the hydrants, hoses and nozzles on the fire main. On a floating or jack-up unit the pump is often a vertical caisson pump or a hydraulically driven submerged pump. A used pump set has to prove its curve and its driver before it can feed your deluge and hydrant demand.
How the firewater supply works
The fire pumps lift seawater into a ring main that runs around the unit with isolation valves between sections. A small jockey pump holds the main at pressure. When pressure drops, or the fire and gas system calls for water, the main pumps start automatically. An emergency fire pump in a separate space, with its own power and suction, keeps water available if a fire takes out the main pump room.
Jack-ups and semisubmersibles usually draw from deep below the hull. Typical arrangements are vertical turbine pumps with long lineshafts in a caisson, electric submersible pumps, or submerged pumps driven hydraulically from a deck power pack.
Configurations
| Type | Driver | What it suits |
|---|---|---|
| Horizontal or vertical centrifugal in a pump room | Electric motor or diesel | Units with sea chests below the waterline |
| Vertical turbine in a caisson | Diesel through a right-angle gear, or electric | Jack-ups and platforms with a long lift to deck |
| Submerged hydraulic pump | Diesel-hydraulic power pack on deck | Deep caissons, no long lineshaft |
| Electric submersible pump | Electric, cable down the caisson | Units with a secure emergency power supply |
Key specifications
| Parameter | Why it matters | Typical units |
|---|---|---|
| Rated flow | Must cover the largest deluge zone plus hydrant demand | m3/h or US gpm |
| Rated pressure | Sets pressure at the most remote hydrant or nozzle | bar or psi |
| NPSH required and suction lift | Decides caisson depth and draft limits | m or ft |
| Driver power | Diesel or motor sizing, and emergency switchboard load | kW or hp |
| Wetted materials | Seawater corrosion and erosion life | Bronze, duplex, super duplex |
Standards and what they ask of a used pump
SOLAS chapter II-2 regulation 10.2 sets minimum hydrant pressures, hose lengths and dual-purpose jet and spray nozzles. Chapter 12 of the FSS Code covers the emergency fire pump. Its capacity must be at least 40 percent of the total required capacity of the main fire pumps, and on cargo ships of 2,000 gross tonnage and above never less than 25 m3/h (110 US gpm). A diesel driver needs a service tank for at least 3 hours at full load, with reserves outside the category A machinery spaces for another 15 hours. MSC.1/Circ.1314 adds that where the emergency pump also feeds a fixed water-based system protecting the machinery space, it must supply that system plus two jets at the required pressure. MSC.1/Circ.1388 asks that available suction head exceed the required head across the normal range of drafts.
Units built to NFPA 20 use listed pumps with a flat curve. An NFPA 20 pump must deliver at least 150 percent of rated flow at no less than 65 percent of rated pressure, and its churn pressure must not exceed 140 percent of rated. NFPA 25 sets weekly or monthly churn runs and an annual flow test.
Failure modes and inspection
- Impeller erosion and cavitation damage, measured against OEM wear ring clearances
- Lineshaft bearings, couplings and alignment on long caisson pumps
- Column pipe and bowl corrosion where the caisson splash zone meets air
- Mechanical seals and packing leaking seawater into bearings
- Diesel starting batteries, air or hydraulic start and the charger
- Right-angle gearbox oil, backlash and bearing noise
- Controller auto-start on pressure drop and on remote command
A performance test with a calibrated flowmeter and pressure gauges, plotted against the certified curve, is the core check. Add vibration readings and an oil analysis for the diesel.
Hydrants, hoses and nozzles
Check the hydrant coupling type against your hoses. Instantaneous, Storz and NST threads do not mix without adapters. Hoses are a wear item, so check their pressure test dates and buy new ones if records are missing. SOLAS asks for dual-purpose nozzles in 12 mm, 16 mm or 19 mm sizes, matched to the space.
Documentation
- Certified factory test curve and the latest field performance test
- Class or listing certificate, such as UL or FM to NFPA 20
- Diesel running hours and overhaul history
- Controller test records and wiring diagrams
- Materials certificates for the pump and column
Integration and recertification
Match flange ratings, column length and suction depth to your caisson and drafts. Check the emergency pump's power source and that it starts from the emergency switchboard or its own diesel. Wire the controller into your fire and gas logic. Recertifying a used pump set usually means an overhaul with new wear rings, seals and bearings, a driver service and a witnessed performance test for class. An unused surplus pump set from a cancelled project is often the best buy if its rating fits. Naventr can arrange a witnessed pump test as part of an inspection. Framo and Sulzer are well-known firewater pump makers offshore. For the systems the pumps feed, see deluge and sprinkler systems.
FAQ
Frequently asked questions
What size emergency fire pump does a drilling unit need?
At least 40 percent of the total required capacity of the main fire pumps, under chapter 12 of the FSS Code, and on cargo ships of 2,000 gross tonnage and above never less than 25 m3/h (110 US gpm). MSC.1/Circ.1314 adds that it must also supply any fixed water system protecting the machinery space plus two jets of water at the required pressure.
What should I check on a used diesel fire pump?
Start with a performance test against the certified curve, using a calibrated flowmeter. Then check engine hours and overhaul records, the starting system, the controller auto-start and the impeller, wear rings and seals for seawater wear.
Are NFPA 20 fire pumps accepted on offshore units?
Often yes, when class and the flag accept the installation as meeting the MODU Code and SOLAS. NFPA 20 pumps are listed to deliver 150 percent of rated flow at no less than 65 percent of rated pressure. Confirm acceptance with class before you buy.
How much fuel does a diesel emergency fire pump need?
Its service tank must hold enough fuel for at least 3 hours at full load under chapter 12 of the FSS Code. Reserves for another 15 hours must be available outside the category A machinery spaces. Check tank size on a used skid against this.